MIC-2510: Is there an option for PI (Polarization Indicator) and DAR (Dielectric Absorption Ratio) measurements?

Yes.

In the device settings define the type of absorption coefficient – depending on the choice the following symbols will be displayed: Ab1, Ab2, or DAR, PI.

In order to measure DAR you must also set the measurement time t1=30s, t2=60s.
In order to measure PI must also set time t3=600s.