MIC-2511

Index: WMGBMIC2511

Insulation resistance meter

Keep up to date with products in the category

Measure insulation resistance up to 2 TΩ

The functional insulation resistance meter Sonel MIC-2511 allows you to measure insulation resistance with a test voltage of up to 2500 V. It surprises with numerous functions hidden in a neat and handy form. Due to its parameters, robust housing with IP65 protection level, low energy consumption from batteries and the possibility of recharging during measurements, the meter is a reliable tool that can be used in many areas. It is perfect for controlling industrial installations and traction networks, it is also successfully used in residential construction. The advantages of this device are especially appreciated by electricians working in maintenance, testing motors, cables and street lighting. The Sonel MIC-2511 meter is also useful for measurements during the construction and maintenance of photovoltaic installations. It is a reliable solution created for the needs of telecommunications network installers and heating network operators,

 

Characteristics

  • Test voltage selected in the range of 50…2500 V : 100 V, 250 V, 500 V, 1000 V, 2500 V or 50…2500 V every 10 V,
  • Measurements of insulation resistance with the voltage of 10 V of the detection loop of fire alarm systems (SAP, SSP)
  • Plotting graphs on the display during measurements
  • Measurements in electrostatic protection zones (EPA)
  • Correction of the insulation resistance result to the reference temperature
  • Continuous indication of measured insulation resistance or leakage current
  • Self-discharge of the measured object’s capacitance after completing the insulation resistance measurement
  • Acoustic determination of five-second time intervals, facilitating the capture of time characteristics
  • Measured measurement times T 1 , T 2 and T 3 for the measurement of one or two absorption coefficients (Ab1, Ab2 or DAR, PI) in the range of 1…600 s
  • Automatic measurement of all resistance combinations of 3-, 4-, 5-wire and power cables using the additional AutoISO-2511 adapter
  • Indication of the actual test voltage during the measurement
  • Measuring current ≤2 mA
  • Protection against measuring live objects
  • Measurement of insulation resistance using the two- and three-wire method

Additional features

  • Leakage current measurement during R ISO measurement
  • Capacitance measurement during R ISO measurement
  • Low-voltage measurement of circuit continuity and resistance
  • Temperature measurement (with the use of an additional ST-1 temperature probe)
  • Measurement of DC and AC voltages in the range of 0…1500 V
  • Memory for 9999 entries, data transmission to a PC via USB cable
  • Battery powered
  • Backlit keyboard
  • The instrument meets the requirements of the EN IEC 61557 standard

Application

Insulation resistance meter with a wide range of applications. It works great both in housing construction, as well as when checking industrial installations or transmission and traction networks. Due to its features – excellent parameters, low energy consumption from the batteries and the possibility of recharging them during measurements, portability and a high degree of tightness of the housing – it is willingly used by electricians working in maintenance, testing motors, cables, street lighting or in construction and maintenance of photovoltaic installations. It perfectly meets the needs of telecommunications network installers and heating network operators, where it is required to control the alarm system of pre-insulated pipes.

Distinguishing features

The meter allows you to measure insulation resistance with a test voltage of up to 2500 V. In the case of testing cables, it automatically discharges their capacitance at the end of the measurement. Together with the PRZ-2 , i.e. a set for measuring resistance in ESD protected zones , it is a comprehensive tool for coordinators dealing with the protection of plants against static electricity.

Thanks to the device, you can control home and industrial electrical installations in terms of safety. Measurements can be easily automated by using the AutoISO-2511 adapter to test the insulation resistance of 3-, 4- and 5-core cables.
MIC-2511 will allow the user to measure the continuity of protective and equipotential bonding with a current greater than 200 mA, in both directions. The meter has a built-in voltmeter for DC and AC voltages up to 1500 V.

The extensive memory of the device allows you to save and send to the computer nearly 10,000 measurement results.

Built-in help system

The device has built-in help screens with measurement diagrams. Thanks to this, it is easy and quick to check how to connect a given system depending on the type of measurement performed.

Communications and software

Measurement data can be transferred to a computer via the USB port. In order to generate a test report in the field of electric shock protection, the Sonel Electrical Measurements program should be used . Saving the downloaded resources to the simplest formats and printing is provided by Sonel Reader .

Specification

Insulation resistance measurement

Measuring range according to IEC 61557-2 for R ISOmin =U ISOnom /I ISOnom …≤ 2 TΩ (I ISO =1.6 mA)

Range Resolution Accuracy
0.0…999.9 kΩ 0.1 kΩ ±(3% in m + 20 digits)
1.000…9.999 MΩ 0.001 MΩ ±(3% in m + 20 digits)
10.00…99.99 MΩ 0.01MΩ ±(3% in m + 20 digits)
100.0…999.9 MΩ 0.1MΩ ±(3% in m + 20 digits)
1.000…9.999 GΩ 0.001 GΩ ±(3% in m + 20 digits)
10.00…99.99 GΩ 0.01GΩ ±(3% in m + 20 digits)
100.0…999.9 GΩ 0.1GΩ ±(3% in m + 20 digits)
1,000…2,000 TΩ 0.001TΩ ±(3% in m + 20 digits)

“wm” – measured value

 

Values ​​of the measured resistance depending on the measuring voltage

Voltage U n Measurement range
50V 50 GΩ
100V 100 GΩ
250V 250 GΩ
500V 500 GΩ
1000V 1.00TΩ
2500V 2.00TΩ

DC and AC voltage measurement

Range Resolution Accuracy
0…1500V 1V ±(3% wm + 2 digits)

frequency range: 45…65 Hz

 

Capacitance measurement

Range Resolution Accuracy
0…999nF 1nF ±(5% wm + 5 digits)
1.00…9.99 μF 0.01μF ±(5% wm + 5 digits)

Measurement of the continuity of protective and equipotential bonding with a current of 200 mA

Measuring range according to IEC 61557-2: 0.10…999 Ω

Range Resolution Accuracy
0.00…19.99 ohms 0.01Ω ±(2% wm + 3 digits)
20.0…199.9 ohms 0.1Ω ±(2% wm + 3 digits)
200…999 Ohms 1 ohms ±(4% wm + 3 digits)

Temperature measurement

Range Resolution Accuracy
-40.0…99.9°C 0.1°C ±(3% wm + 8 digits)
-40.0…211.8°F 0.1°F ±(3% wm + 16 digits)

Resistance measurement in EPA zones

Range Resolution Accuracy
for Un = 10V
0.0…999.9 kΩ 0.1 kΩ ±(8% in m + 20 digits)
1.0…9.999 MΩ 0.001 MΩ ±(8% in m + 20 digits)
10.00…99.99 MΩ 0.01MΩ ±(8% in m + 20 digits)
100.0…999.9 MΩ 0.1MΩ ±(8% in m + 20 digits)
1.0…10.0 GΩ 0.1GΩ ±(8% in m + 20 digits)
for U n = 100 V
0.0…999.9 kΩ 0.1 kΩ ±(3% in m + 20 digits)
1.000…9.999 MΩ 0.001 MΩ ±(3% in m + 20 digits)
10.00…99.99 MΩ 0.01MΩ ±(3% in m + 20 digits)
100.0…999.9 MΩ 0.1MΩ ±(3% in m + 20 digits)
1,000…9,999 GΩ 0.001 GΩ ±(3% in m + 20 digits)
10.00…99.99 GΩ 0.01GΩ ±(3% in m + 20 digits)
100.0…200.0 GΩ 0.1GΩ ±(8% in m + 20 digits)
for U n = 500 V
0.0…999.9 kΩ 0.1 kΩ ±(3% in m + 20 digits)
1.000…9.999 MΩ 0.001 MΩ ±(3% in m + 20 digits)
10.00…99.99 MΩ 0.01MΩ ±(3% in m + 20 digits)
100.0…999.9 MΩ 0.1MΩ ±(3% in m + 20 digits)
1,000…9,999 GΩ 0.001 GΩ ±(3% in m + 20 digits)
10.00…99.99 GΩ 0.01GΩ ±(3% in m + 20 digits)
100.0…999.9 GΩ 0.1GΩ ±(8% in m + 20 digits)
1000 GΩ 1 GΩ ±(8% in m + 20 digits)