MRU-10

Catalog index: WMGBMRU10

Earth Resistance Meter

 

Keep up to date with products in the category

Basic grounding measurements under all conditions

The Sonel MRU-10 earthing resistance meter - a compact and easy to use meter designed for earthing measurements using the technical method and for earth resistance measurements using the bipolar method.

The handy Sonel MRU-10 meter is characterised by exceptional ease of use while providing accurate results. The device is highly resistant to the occurrence of interference voltages. This is a basic type of meter that allows the quality of the earthing system to be assessed based on the test results obtained. Due to its ergonomic shape, robust casing and large and easy to read display, the MRU-10 meter is ideal for use in various areas. The device is ideal for electrical installation work. It is also a suitable working tool for technicians and measuring engineers involved in checking earthing.

Earthing resistance measurements

  • 3-pole method – measurement of earthing systems using auxiliary probes
  • 2-pole method

Features

  • resistance of auxiliary electrodes RH and RS
  • measurement of interference voltage to 100 V
  • indication of battery state
  • selection of maximum measuring voltage (25 V and 50 V)
  • Auto-OFF function

Overview

MRU-10 is a simple meter that allows you to measure grounding by the use of the technical method and to measure grounding resistance by the use of the 2-pole method. The instrument is easy to handle, resistive to interference, and highly accurate. MRU-10 is a basic device that allows checking the quality of the grounding system on the basis of the received measurement result. Its ergonomic shape, durable and firm housing, as well as big and clear display make this instrument ideal to use both in the field and most working environments. The device is simple to operate and intuitive. It is the best choice for electrical installations contractors, technicians, and professionals dealing with grounding measurements.

Specification

It allows to:

  • measure earthing resistance using auxiliary electrodes,
  • measurement of resistance of auxiliary electrodes RS and RH,
  • measurement of interference voltage,
  • measurement in the presence of interference voltage in the power network with frequency 50 Hz and 60 Hz,
  • selection of maximum measuring voltage (25 V and 50 V),
  • indication of battery state.

 

Measurement of interference voltage UN (RMS)

Range Resolution Accuracy
0…100 V 1 V ±(10% m.v. + 1 digit)

Measurement of earthing resistance (method 3-pole)
measurement range to IEC 61557-5:2007: 0,53 Ω…9999 Ω (for 50 V)

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.
  • measurement current: under short circuit >20 mA,
  • voltage on open terminals: selectable 25 V AC or 50 V AC,
  • frequency of measurement current: 125 Hz (for networks 50 Hz) or 150 Hz (for 60 Hz),
  • selection of measuring frequency in settings.

Measurement of earthing resistance (method 2-pole)

Range Resolution Accuracy
0,01…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200,0…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.

Measurement of earthing resistance (method 2-pole) RH and RS

Range Resolution Accuracy
0…999 Ω 1 Ω ±8% m.v.
1,00…9,99 kΩ 0,01 Ω
10,0…19,9 kΩ 0,1 Ω

Electric security:

  • type of insulation: double, according to EN 61010-1 and IEC 61557,
  • measurement category: CAT IV 150 V acc. to EN 61010-1,
  • protection class acc. to EN 60529: IP67.

Rated operational conditions:

  • operation temperature: -10…+50°C,
  • storage temperature: -20…+60°C,
  • humidity: 20…90%.

Other technical data:

  • LCD display: segment, backlit,
  • dimensions: 221 x 102 x 62 mm,
  • number of measurements (RE3P) carried out of set of batteries: > 3000