It allows to take the measurements of:
- earthing resistance using auxiliary electrodes,
- selective earth resistance measurement with Clamp (no influence from parallel earth, no opening of rusty junctions if needed
- earthing resistance using auxiliary electrodes and clamp (for measurements of multiple earthing),
- earthing resistance using double clamps (for measurement of earthing when it is impossible to use auxiliary electrodes),
- ground resistivity (Wenner method),
- continuity of equipotential bondings and protective
- conductors (meeting the requirements IEC 60364) with auto-zero function – with current 200mA.
Additionally:
- measurement of resistance of auxiliary electrodes RS and RH,
- measurement of interference voltage,
- measurement in the presence of interference voltage in the power network
- with frequency 50Hz, 60Hz,
- selection of maximum measuring voltage (25V and 50V),
- introducing the distance between the electrodes for the resistivity in metres (m) and feet (ft),
- memory of 990 measurements (10 banks of 99 cells each),
- calibration of clamp used,
- data transmission to the computer (USB),
- indication of battery state.
Measurement of interference voltage UN (RMS)
Range | Resolution | Accuracy |
0…100 V | 1 V | ±(10% m.v. + 1 digit) |
Measurement of continuity of equipotential bondings and protective conductors (Rcont)
measurement range to IEC 61557-4:2007: 0,13 Ω…1999 Ω
Range | Resolution | Accuracy |
0,00…9,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
10,0…99,9 Ω | 0,1 Ω | |
100…19.9K Ω | 1 Ω |
• measurement current: under short circuit >200mA
• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz (for networks 60 Hz)
Measurement of earthing resistance (method 3- and 4-pole)
measurement range to IEC 61557-5:2007: 0,53 Ω…9999 Ω (dla 50 V)
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
20,0…199,9 Ω | 0,1 Ω | |
200,0…1999 Ω | 1 Ω | ±2% m.v. |
2000…19.9K Ω | 1 Ω | ±2% m.v. |
• measurement current: under short circuit >20 mA,
• voltage on open terminals: selectable 25 V AC or 50 V AC,
• frequency of measurement current: 125 Hz (for networks 50 Hz) or 150 Hz (for 60 Hz).
Measurement of multiple earthing esistance with using the clamp and auxiliary electrodes (3p + clamp)
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
20,0…199,9 Ω | 0,1 Ω | |
200…1999 Ω | 1 Ω | ±2% m.v. |
±2% m.v. |
• voltage on open terminals: selectable 25 V AC or 50 V AC,
• measurement current: under short circuit >20 mA,
• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz (for networks 60 Hz)
Measurement of resistance of auxiliary electrodes RH i RS
Range | Resolution | Accuracy |
0…999 Ω | 1 Ω | ±(5% m.v.+ 8 digits) |
1,00k…9,99 kΩ | 0,01 kΩ | |
10,0k…19,9 kΩ | 0,1 kΩ |
Measurement of multiple earthing resistance with using double clamps
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(10% m.v. + 8 digits) |
20,0…99,9 Ω | 0,1 Ω | ±(20% m.v. + 3 digits) |
• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz
(for networks 60 Hz)
Measurement of ground resistivity
Measurement method: Wenner, ρ=2πLRE
Range | Resolution | Accuracy |
0,00…9,99 Ωm | 0,01 Ωm | depending on measurement accuracy RE with 4p method, but not less than ±1 digit |
10,0…99,9 Ωm | 0,1 Ωm | |
100…999 Ωm | 1 Ωm | |
1,00…9,99 kΩm | 0,01 kΩm | |
10,0…99,9 kΩm | 0,1 kΩm | |
100…999 kΩm | 1 kΩm |
L – distance between probes: 1…50 m.. or 1…150 ft
Electric security:
- type of insulation: double, according to EN 61010-1 i IEC 61557,
- mesurement category: CAT III 300V wg EN 61010-1,
- protection class acc. to EN 60529: IP65,
Rated operational conditions:
- operation temperature: -10…+55°C,
- storage temperature: -20…+80°C,
- humidity: 20…90%,
Other technical data:
- LCD display: segment, backlit,
- dimensions: 200x150x74 mm.